Computer Room Air Handler (CRAH)
Plain-English definition
A data-hall air unit that pulls warm exhaust air across finned chilled-water coils and pushes cooled air back toward server intakes using variable-speed fans. Unlike a self-contained air conditioner, it contains no refrigerant compressor; instead, a modulating water valve regulates chilled water delivered from a central plant.
Why it matters on shift
CRAH units are the primary air-side bridge between server racks and the facility chilled-water loop. Understanding whether an overheating hall is starved of airflow or starved of chilled-water flow prevents operators from lowering air setpoints against a maxed-out water valve.
Illustrative operational example
In an illustrative hall, four perimeter CRAHs receive 11.5°C plant chilled water, open their modulating valves to 68%, and deliver 19.5°C supply air into a contained cold aisle.
Scope, code & safety boundary
CRAH discharge air temperature is a facility control setpoint, not the server equipment-inlet rating; always check OEM coil pressure limits and site SOPs before overriding fan or valve controls.
Related courses & interactive lab practice
Air, chilled-water & liquid cooling
Facility, rack & safety foundations
Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.