Calculating stagnant coolant temperature rise rate inside a 120 kW rack
Illustrative thermal-inertia calculation: One 120 kW AI rack rejects 80% of its heat (Q_liq = 96 kW = 96 kJ/s) into its internal cold plates and rack manifold holding V = 12.0 liters of PG25 coolant (density ρ = 1.02 kg/L, specific heat c_p = 3.92 kJ/kg·°C; ignoring copper cold-plate metal mass for conservative fluid-only upper bound).
- Step 1
Calculate fluid thermal capacitance inside the rack with units: Mass m = 12.0 L × 1.02 kg/L = 12.24 kg. Thermal capacitance C_th = 12.24 kg × 3.92 kJ/kg·°C ≈ 48.0 kJ/°C.
- Step 2
Calculate adiabatic fluid temperature rise rate if flow = 0 L/min: dT/dt = Q_liq ÷ C_th = (96 kJ/s) ÷ (48.0 kJ/°C) = +2.0°C per second (even counting ~25 kg of copper cold plates/manifolds adds ~9.6 kJ/°C, yielding ~1.67°C/second).
- Step 3
Compute time to an illustrative +20°C excursion under these stated assumptions: Δt = 20°C ÷ 1.67°C/s ≈ 12 seconds (or 10 seconds fluid-only at 2.0°C/s). Under this modeled load and fluid volume, manual walkdowns cannot outrun a complete secondary flow stop, so pump power continuity, automatic standby transfer, and thermal protection must match the validated site and OEM design.
Optional depth · Scope boundaries & modeling assumptions
Scope & assumptions: Exact rack fluid volume (typically 8 to 25 L per cabinet plus header volume), copper mass, and GPU hardware thermal-throttle thresholds (~83°C to 90°C junction) vary by OEM rack architecture; actual thermal ride-through, pump transfer timing, and electrical backing requirements are conditional on the validated site and OEM design.