Scaling a 4 to 20 mA pressure transmitter and spotting wire break vs zero pressure
Illustrative transmitter check: Chilled-water differential pressure transmitter DPT-204 is scaled 0 to 50.0 psi across a 4.0 to 20.0 mA current loop (span = 16.0 mA). Controls asks you to interpret two field readings.
- Step 1
Convert a healthy 11.68 mA loop reading into psi with units: Fraction of span = (11.68 mA − 4.00 mA) ÷ 16.00 mA = 7.68 ÷ 16.00 = 0.480 (48.0%). Pressure = 0.480 × 50.0 psi = 24.0 psi.
- Step 2
Distinguish real 0.0 psi pump loss from a cut wire: If pumps stop and pipes sit at 0.0 psi differential, a healthy transmitter outputs EXACTLY 4.00 mA ('live zero').
- Step 3
Spot instrumentation fault: If the PLC analog input measures 0.00 mA (reading '-12.5 psi' unclipped or 'Sensor Fault'), the 24 V DC loop wire is open or a fuse blew; do NOT start emergency pumps blindly before checking adjacent pressure gauges.
Optional depth · Scope boundaries & modeling assumptions
Scope & assumptions: Sensor signal types (4 to 20 mA, 0 to 10 V DC, Pt100/1000 Ω RTD, or digital Modbus/BACnet MS/TP) and stale-data timeout flags depend on site PLC and BMS engineering standards.