Selective Overcurrent Coordination and Time-Current Curves (TCC)
Plain-English definition
Engineering upstream and downstream circuit breaker pickup thresholds and time delays so that only the protective device immediately upstream of a short circuit or overload opens, leaving healthy sibling feeders and upstream UPS buses uninterrupted.
Why it matters on shift
When coordination curves overlap, or after someone dials an upstream breaker's instantaneous pickup down without an engineering study, a single shorted server PSU can skip the rack breaker and trip an entire 400 kVA floor PDU.
Illustrative operational example
In an illustrative time-current study, a 20 A rack branch breaker clears a bolted fault in 8 ms while the upstream 225 A RPP feeder breaker waits in short-time delay, confining the outage to one cabinet cord.
Scope, code & safety boundary
Never alter electronic trip-unit dials (long-time, short-time, instantaneous, or ground-fault settings) in the field without a stamped coordination and arc-flash study; slower clearing times directly raise arc-flash incident energy.
Related courses & interactive lab practice
Critical power & dual-path feeds
Maintenance procedures, hold gates & response
Practice live readings and switching in "2N Blackout & Live Diesel Synchroscope" with no login required.
Primary standards & technical references