Two-Person Reader-Doer Execution and Circle-and-Slash Placekeeping
Plain-English definition
A two-person switching method that prevents operating the wrong breaker or valve. The Reader holds the written Method of Procedure (MOP) and reads one step aloud. The Doer touches the equipment nameplate, reads the tag back word for word, waits for confirmation, performs the action, and marks the step complete.
Why it matters on shift
Rows of identical gray switchgear doors and valve manifolds trick human memory. Point-and-read verification paired with circle-and-slash placekeeping prevents skipped steps and wrong-unit actions when radio calls interrupt a crew.
Illustrative operational example
In an illustrative MOP step to close Valve CHW-ISO-2B, the Reader circles the step number when starting, checks that the Doer's finger is on engraved brass tag 'CHW-ISO-2B' rather than 'CHW-ISO-2A', authorizes motion, and draws a slash through the circle once closed.
Scope, code & safety boundary
Never batch multiple steps from memory to save walking. Whenever a crew pauses for an alarm or radio call, re-anchor at the last slashed step and re-check preconditions before continuing.