Volumetric Coolant Flow Rate (L/min and GPM)

#volumetric-flow-rate
Also called
  • flow rate
  • L/min
  • LPM
  • GPM
  • coolant L/min per kW

Plain-English definition

The volume of liquid or air passing through a pipe, manifold, or cold plate per unit time, commonly expressed in liters per minute (L/min) or US gallons per minute (GPM; 1 GPM ≈ 3.785 L/min) for liquid loops.

Why it matters on shift

Direct-to-chip cold plates specify a minimum L/min per kW (often ~1.0 to 1.5 L/min per kW depending on fluid and max ΔT) to maintain turbulent internal heat transfer and keep chip temperatures below throttling thresholds.

Illustrative operational example

In the illustrative Hall D CDU lab, restoring 25.3 psi manifold ΔP delivers roughly 860 L/min across the eight-rack pod (~107 L/min per 120 kW rack for the ~90 kW liquid share).

Scope, code & safety boundary

Ultrasonic and turbine flowmeters require straight upstream/downstream pipe diameters and accurate fluid-type configuration (water vs PG25) to avoid 5 to 15% flow reading errors.

Related courses & interactive lab practice

AdvancedRS-203~85 min open lessons
AI Density Lab

High-density AI cooling & commissioning

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).