Generator Speed Governor and Automatic Voltage Regulator (AVR) Trim
Plain-English definition
The twin closed-loop controllers on a standby generator set: the electronic speed governor meters engine fuel rack input to regulate shaft RPM and electrical frequency (Hz), while the Automatic Voltage Regulator (AVR) adjusts alternator field excitation current to hold terminal voltage (V).
Why it matters on shift
Understanding that fuel controls frequency (and real kW load sharing) whereas excitation controls voltage (and reactive kVAR sharing) lets operators interpret synchroscope drift and generator transient recovery accurately.
Illustrative operational example
In the illustrative Generator Yard mission, raising governor trim lifts Gen G2 from 59.1 Hz to 60.0 Hz to slow synchroscope needle rotation, while AVR trim raises terminal voltage from 466 V to 480 V.
Scope, code & safety boundary
Improper droop or isochronous governor/AVR settings across paralleled generators cause real-power motoring or reactive-current hunting; parameter changes belong strictly to qualified commissioning engineers.