Lockout / Tagout (LOTO) and Live-Dead-Live Zero-Energy Verification
Plain-English definition
The hazardous-energy isolation discipline requiring every exposed worker to place an individually keyed personal lock and tag on each physical electrical, mechanical, hydraulic, or chemical isolation point and verify zero stored energy in the field before work starts.
Why it matters on shift
BMS screens, auxiliary breaker flags, and verbal assurances can lie when linkages stick or secondary backfeeds exist; only personal physical locks plus a verified live-dead-live meter check or pressure bleed guarantee an isolation boundary.
Illustrative operational example
Before unbolting an illustrative chilled-water pump coupling, a mechanic locks out the VFD disconnect, bleeds casing pressure to 0 psi, and sees the electrician prove 0 V phase-to-phase and phase-to-ground using a meter tested on a known live source before and after.
Scope, code & safety boundary
Never hang your work on a supervisor's lock alone: every person crossing the hazard boundary applies a personal lock to the group lockbox, and teams must isolate secondary sources such as UPS control power, springs, or elevated piping head.