Auxiliary Contact Status vs Proof-of-Flow Telemetry
Plain-English definition
The diagnostic discipline of verifying physical fluid movement through direct process measurements (differential pressure, flowmeters, motor current in amps, and temperature split) rather than trusting a starter auxiliary contact or BMS 'Run' command bit alone.
Why it matters on shift
A contactor auxiliary switch only proves an electrical relay closed: a sheared pump coupling, closed isolation valve, vapor-locked impeller, or tripped VFD output can leave zero flow behind a green 'Run' icon.
Illustrative operational example
In the illustrative NOC triage lab, overlaying pump CHW-P2B motor current (0.0 A) with header ΔP (collapsed from 24.0 to 4.2 psi) provides indisputable proof of flow loss.
Scope, code & safety boundary
During commissioning and incident response, always corroborate command state against at least two coupled physical trends (amps, ΔP, flow, and ΔT).
Related courses & interactive lab practice
Building/power monitoring & alarm triage
Air, chilled-water & liquid cooling
Practice live readings and switching in "NOC Alarm Storm & 1ms SOE Triage" with no login required.