Wrap-Around Maintenance Bypass (MBB)
Plain-English definition
An external switchgear breaker path routed completely around a UPS lineup so electrical technicians can transfer load onto synchronized static bypass first, close the external MBB breaker make-before-break, and then isolate and lock out the entire UPS chassis.
Why it matters on shift
Closing an external wrap-around MBB breaker while the UPS inverter is still actively regulating, without transferring to synchronized internal static bypass first, back-feeds raw AC directly into the inverter bridge and risks tripping the bus.
Illustrative operational example
In an illustrative UPS preventive maintenance MOP, a two-person reader-doer crew verifies companion Bus B carries <45% load, confirms UPS-A transfers to synchronized Static Bypass, closes MBB, and opens UPS-A output/input breakers.
Scope, code & safety boundary
Wrap-around bypass switching sequences are strictly specific to each UPS OEM and switchgear interlock scheme; qualified electrical personnel must follow the exact stamped site MOP.