Static Transfer Switch (STS)
Plain-English definition
A high-speed solid-state switching cabinet using back-to-back Silicon-Controlled Rectifiers (SCRs) to switch single-corded loads or Floor PDUs between two synchronized UPS sources in roughly 4 milliseconds, fast enough that downstream server power supplies stay continuously online.
Why it matters on shift
An STS provides fast source failover for legacy single-corded gear or catcher architectures, yet it sits physically inline as a shared cabinet and carefully blocks cross-connecting a dead short circuit onto the healthy alternate source.
Illustrative operational example
Following an illustrative branch fault that briefly sags Source 1 voltage below 85%, an STS transfers a downstream PDU to synchronized Source 2 in 4.2 ms, captured accurately only in 1 ms EPMS SOE logs.
Scope, code & safety boundary
Dual-corded A/B servers rarely need rack or floor STSs; verify upstream UPS phase synchronization before performing planned STS preferred-source transfers.