Stranded Capacity and the Multi-Constraint Sellable Ceiling
Plain-English definition
Paid-for power, cooling, space, structural weight, or network port capacity trapped unusable inside a data hall because one single resource dimension hits its safe N+1/2N ceiling before the other four dimensions fill up.
Why it matters on shift
Selling customer racks based solely on spare UPS megawatts when cooling coils or floor-slab load limits are already tapped out creates summer thermal throttling or stranded electrical capex.
Illustrative operational example
In an illustrative five-constraint hall ledger with 4.0 MW UPS capacity, 3.2 MW peak-summer cooling rejection, and 4.5 MW cabinet space, sellable hall capacity is strictly min(4.0, 3.2, 4.5) = 3.2 MW, stranding 0.8 MW of UPS gear until cooling upgrades.
Scope, code & safety boundary
Capacity ledgers must reconcile nameplate ratings against worst-case single-failure N+1/2N states and summer design-day derating rather than mild winter averages.