Stratified Chilled-Water Thermal Storage Tank (TES Buffer)

#stratified-chilled-water-tank
Also called
  • TES
  • TES tank
  • Thermal Energy Storage Tank
  • thermal ride-through tank
  • thermocline tank

Plain-English definition

An insulated vertical vessel connected to the chilled-water loop that separates dense cold supply water at the bottom from lighter warm return water at the top across a thin natural density boundary (thermocline), supplying continuous cooling while chillers restart after an electrical disturbance.

Why it matters on shift

Even when UPS batteries keep servers and pumps online through a blackout, mechanical chillers drop offline during generator transfer; thermal storage bridges those critical minutes so high-density halls do not overheat.

Illustrative operational example

On North Campus, an illustrative 50,000-gallon stratified tank with an 11.5°C lower supply zone provides roughly 8 minutes of chilled-water ride-through while standby generators synchronize and chillers re-stage.

Scope, code & safety boundary

Excessive charging or discharging velocity through damaged internal diffusers destroys stratification by mixing warm and cold layers, cutting usable ride-through time sharply.

Related courses & interactive lab practice

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

BeginnerRS-102~87 min open lessons
Utility to Rack

Critical power & dual-path feeds

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).