Sympathy Alarm (Cascading Downstream Chatter)
Plain-English definition
A secondary alert generated by healthy downstream equipment reacting momentarily to an upstream disturbance, such as a brief utility voltage sag or header pressure dip, rather than suffering an independent local component failure.
Why it matters on shift
Recognizing sympathy cascades stops shift leads from dispatching technicians to inspect sixteen healthy air handlers while the single upstream feeder event or single latched pump lockout goes unaddressed.
Illustrative operational example
When Feeder B dips to 71% nominal for 140 ms in the illustrative NOC lab, sixteen CRAH EC-fan drives log DC-bus undervoltage ride-through advisories at +186 ms and self-clear automatically.
Scope, code & safety boundary
Never dismiss an assumed sympathy alarm without verifying process recovery: confirm downstream fans or pumps actually returned to speed and flow rather than latching off.