Variable-Frequency Drive (VFD) and DC-Bus Ride-Through
Plain-English definition
Power-electronics motor controller that rectifies AC supply into a DC capacitor bus and synthesizes variable-frequency, variable-voltage AC output to control pump, fan, or chiller compressor speed smoothly while governing acceleration ramps and voltage-sag ride-through.
Why it matters on shift
VFDs unlock cubic-law energy savings on hydronic pumps and fans, yet differences in DC-bus undervoltage trip thresholds and auto-restart parameters determine whether cooling survives a 100 to 200 ms utility sag.
Illustrative operational example
During the illustrative 140 ms Feeder B voltage sag, CRAH EC-fan drives ride through via kinetic/DC-bus buffering, whereas Pump CHW-P2B's VFD trips offline on DC-bus undervoltage lockout.
Scope, code & safety boundary
Enabling automatic flying-start VFD restarts after power dips must be coordinated with mechanical backspin limits, water-hammer analysis, and generator step-load sequencing.