Water-Cooled Centrifugal Chiller
Plain-English definition
A high-capacity vapor-compression refrigeration machine that uses a high-speed rotating impeller to compress refrigerant, absorbing heat from the building chilled-water evaporator loop and rejecting that heat plus compressor work into a condenser-water loop served by cooling towers or adiabatic coolers.
Why it matters on shift
Chiller compressors dominate cooling-plant electrical load during peak heatwaves. Staging the right number of chillers avoids both high-temperature chilled-water alarms (under-staged) and poor part-load surge or excessive auxiliary pump/condenser draw (over-staged).
Illustrative operational example
In the illustrative 8 MW Central Plant lab, once wetted WSE pre-cools return water from 24.0°C to 20.6°C, staging down from four chillers to two series chillers delivers 12.1°C primary CHW while lowering PUE from 1.25 to 1.16.
Scope, code & safety boundary
Chillers enforce minimum evaporator flow, oil differential, and anti-recycle timers; after a power transfer, compressors can take several minutes to reload unless fast-restart options and thermal storage are engineered.