Waterside Economizer (WSE)

#waterside-economizer
Also called
  • WSE
  • free-cooling heat exchanger
  • integrated waterside economizer
  • series pre-cooling

Plain-English definition

A heat-rejection coil or plate-and-frame heat exchanger arrangement that uses cool outdoor ambient conditions, via a cooling tower, dry cooler, or adiabatic fluid cooler, to pre-cool or fully cool return chilled water before or instead of running mechanical chiller compressors.

Why it matters on shift

In series pre-cooling plants, every degree removed by the economizer reduces mechanical lift on downstream chillers, allowing compressors to unload or stage off for substantial PUE savings.

Illustrative operational example

In our illustrative 8 MW heatwave scenario (24.0°C return CHW, 36.0°C DB / 18.5°C WB), dry WSE mode locks out in bypass, whereas Stage 1 adiabatic wetting pre-cools return water to 20.6°C so two chillers hold 12.1°C CHW at PUE 1.16.

Scope, code & safety boundary

Whenever outdoor heat-sink temperature plus approach exceeds return chilled-water temperature, a 3-way bypass valve must lock out the economizer coil so ambient air does not add heat to the return loop.

Explanatory diagram · Dry fluid cooler & cooling tower yardDry-Bulb vs Wet-Bulb Heat-Rejection Floors and Positive Approach Temperature
Two-column comparison at 32.0 degrees Celsius dry-bulb and 20.0 degrees Celsius wet-bulb contrasting a dry fluid cooler leaving at 37.0 degrees Celsius (+5.0 degrees Celsius approach) against a cooling tower leaving at 24.5 degrees Celsius (+4.5 degrees Celsius approach).

Passive heat-rejection equipment always leaves warmer than its outdoor sink floor by a positive approach temperature: dry coolers approach outdoor dry-bulb, while evaporative towers and adiabatic coolers approach outdoor wet-bulb.

Read plain-text walkthrough of this diagram

Two-column comparison at an illustrative outdoor condition of 32.0 degrees C dry-bulb and 20.0 degrees C wet-bulb (roughly 32% relative humidity at sea level). Column 1 (Dry Fluid Cooler) uses zero air-side evaporation water and is bounded by the 32.0 degrees C dry-bulb floor, leaving at an illustrative 37.0 degrees C (+5.0 degrees C approach). Column 2 (Cooling Tower / Adiabatic Evaporative) evaporates water to lower the air-side sink to the 20.0 degrees C wet-bulb floor, leaving at an illustrative 24.5 degrees C (+4.5 degrees C approach). Neither passive system can cool fluid below its respective sink floor without mechanical chiller compressor work.

Related courses & interactive lab practice

IntermediateRS-302~75 min open lessons
Resource Ledger

Energy, water & capacity accounting

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "35 kW Hot/Cold Aisle Containment Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).