RackscaleData Center Institute
Search & browse all 146 entries

Coolant Distribution Unit (CDU)

#coolant-distribution-unit
Also called
  • CDU
  • liquid-to-liquid CDU
  • in-row CDU
  • in-rack CDU

Plain-English definition

A packaged hydronic skid or rack appliance containing a heat exchanger, redundant variable-speed pumps, fine strainers, expansion volume, and dew-point/pressure controls that isolates building chilled water (FWS) from the clean secondary coolant loop (TCS) feeding high-density IT racks.

Why it matters on shift

The CDU is the operational boundary between Facilities and IT in high-density pods: it regulates secondary supply temperature safely above room dew point while holding precise manifold differential pressure during rapid GPU load steps.

Illustrative operational example

In the illustrative Hall D mission, switching CDU-2 from fouled Basket A to clean Basket B, raising supply to 23.0°C (+4.5°C above 18.5°C dew point), and setting pumps to 82% restores 25.3 psi manifold ΔP.

Scope, code & safety boundary

Liquid-to-air CDUs reject heat into hall air whereas liquid-to-liquid CDUs reject heat into facility water; verify CDU redundancy, leak-rope interlocks, and OEM pressure limits before opening rack isolation valves.

Explanatory diagram · CDU skid, duplex strainers & rack quick-disconnectsFacility Water System (FWS) vs Technology Cooling System (TCS)
Three-zone liquid cooling schematic showing 12.0 degrees Celsius Facility Water System plant piping on the left, a CDU stainless plate heat exchanger with 25 micron strainer and dew-point guard in the center, and a 24.0 degrees Celsius Technology Cooling System rack manifold loop on the right.

A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.

Read plain-text walkthrough of this diagram

Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.

Related courses & interactive lab practice

AdvancedRS-203~85 min open lessons
AI Density Lab

High-density AI cooling & commissioning

BeginnerRS-103~85 min open lessons
Thermal Reality

Air, chilled-water & liquid cooling

Free interactive simulator
Campus Shift · 6-Mission Browser Lab

Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.

Primary standards & technical references

Practice with the equipment

Try this concept in a live scenario.

Walk through six free guided browser missions in Campus Shift, or study all nine self-paced courses from Beginner to Advanced at $399 self-paced tuition ($1,600 list, save $1,201).