Coolant Distribution Unit (CDU)
Plain-English definition
A packaged hydronic skid or rack appliance containing a heat exchanger, redundant variable-speed pumps, fine strainers, expansion volume, and dew-point/pressure controls that isolates building chilled water (FWS) from the clean secondary coolant loop (TCS) feeding high-density IT racks.
Why it matters on shift
The CDU is the operational boundary between Facilities and IT in high-density pods: it regulates secondary supply temperature safely above room dew point while holding precise manifold differential pressure during rapid GPU load steps.
Illustrative operational example
In the illustrative Hall D mission, switching CDU-2 from fouled Basket A to clean Basket B, raising supply to 23.0°C (+4.5°C above 18.5°C dew point), and setting pumps to 82% restores 25.3 psi manifold ΔP.
Scope, code & safety boundary
Liquid-to-air CDUs reject heat into hall air whereas liquid-to-liquid CDUs reject heat into facility water; verify CDU redundancy, leak-rope interlocks, and OEM pressure limits before opening rack isolation valves.
A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.
Read plain-text walkthrough of this diagram
Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.
Related courses & interactive lab practice
High-density AI cooling & commissioning
Air, chilled-water & liquid cooling
Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.