Technology Cooling System (TCS)
Plain-English definition
The closed, tightly filtered secondary liquid circuit that circulates high-purity treated water or an inhibited water-glycol mixture between the secondary side of a Coolant Distribution Unit, row/rack manifolds, and the cold plates inside IT servers.
Why it matters on shift
Because cold-plate microchannels can measure fractions of a millimeter across, TCS fluid cleanliness, pH, inhibitor chemistry, and dew-point temperature control directly govern accelerator reliability and hardware warranties.
Illustrative operational example
In the illustrative Hall D Row 8 pod, the TCS circulates 25 µm-filtered inhibited PG25 coolant at 23.0°C and 25.3 psi manifold differential pressure across eight 120 kW GPU racks.
Scope, code & safety boundary
Every wetted metal and elastomer in the TCS loop (wetted stainless steel, copper cold plates, EPDM hoses, and brazed joints) must match the approved wetted-materials compatibility list to prevent galvanic corrosion.
A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.
Read plain-text walkthrough of this diagram
Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.