Facility Water System (FWS)
Plain-English definition
In ASHRAE and Open Compute liquid-cooling architecture, the building-side piping circuit that delivers cooling water from central chillers, cooling towers, or dry coolers up to the primary side of a Coolant Distribution Unit (CDU), remaining hydraulically isolated from IT racks.
Why it matters on shift
Separating the large-volume Facility Water System from the clean rack loop protects microscopic cold-plate channels from building-pipe scale and bounds maximum fluid volume inside the white space.
Illustrative operational example
ASHRAE defines facility-water supply classes such as W17, W27, W32, and W40; an illustrative W27 loop supplies up to 27°C building water to CDUs so dry or adiabatic coolers can run compressor-free most of the year.
Scope, code & safety boundary
Never cross-connect Facility Water System piping directly into server cold-plate manifolds unless the system is explicitly engineered as a single-loop filtered architecture approved by the IT OEM.
A Coolant Distribution Unit (CDU) transfers heat across a stainless plate heat exchanger while keeping building chilled water physically separate from the filtered, chemistry-controlled coolant inside server cold plates.
Read plain-text walkthrough of this diagram
Zone 1 shows the building Facility Water System supplying 12.0 degrees Celsius chilled water and returning 19.0 degrees Celsius water via a modulating two-way valve without entering white-space racks. Zone 2 shows the CDU 316L stainless brazed-plate heat exchanger, N+1 variable-speed pumps, 25 micron strainer, and dew-point guard holding supply at least 3.0 degrees Celsius above the 13.8 degrees Celsius hall dew point. Zone 3 shows the Technology Cooling System delivering 24.0 degrees Celsius clean inhibited coolant across quick-disconnect valves to GPU and CPU cold plates (78% heat) while air cooling removes the remaining 22% rack heat.
Related courses & interactive lab practice
High-density AI cooling & commissioning
Air, chilled-water & liquid cooling
Practice live readings and switching in "120 kW GPU Direct-to-Chip CDU & Strainer Lab" with no login required.