4 to 20 mA Live-Zero Current Loop and RTD Temperature Sensing
Plain-English definition
Industrial analog instrumentation pairing platinum Resistance Temperature Detectors (RTDs, whose electrical resistance rises predictably with temperature) and 4 to 20 milliampere current transmitters where 4 mA represents the bottom of scale (live zero) and 0 mA immediately reveals a broken wire or failed power supply.
Why it matters on shift
Current loops resist voltage drop across long data-hall cable runs and immediately distinguish a true 0 psi differential-pressure reading (4.0 mA) from a severed sensor cable (0.0 mA wire-break fault).
Illustrative operational example
On an illustrative 0 to 50 psi chilled-water ΔP transmitter scaled to 4 to 20 mA, 4.0 mA equals 0.0 psi, 12.0 mA equals 25.0 psi, and 0.0 mA triggers an immediate sensor open-circuit diagnostic.
Scope, code & safety boundary
Shielded instrument cables should be grounded at one end per OEM wiring rules and routed away from high-voltage VFD motor leads to prevent electromagnetic noise.