Polling Interval, Change-of-Value (COV) Deadband, and Stale Telemetry
Plain-English definition
A frozen telemetry value on an operator console caused by a hung field gateway, dropped network poll, sensor fault, or misconfigured Change-of-Value (COV) deadband, where the screen continues displaying the last cached number without updating.
Why it matters on shift
Real physical temperatures and pressures exhibit tiny natural micro-fluctuations; a suspiciously dead-flat reading that disagrees with adjacent probes and coupled physics can trick crews into emergency actions for a phantom hot spot.
Illustrative operational example
In the illustrative NOC Alarm Storm lab, return-air tag RAT-A4 sits frozen at exactly 49.00°C for 17 minutes (0.00°C variance) while adjacent sensors RAT-A3 (31.0°C) and SAT-A4 (19.2°C) read normal.
Scope, code & safety boundary
Configure BMS graphics to flag bad-quality, comm-fail, and last-update age visibly, and cross-check at least two independent physical points before overriding plant cooling.
Related courses & interactive lab practice
Building/power monitoring & alarm triage
Air, chilled-water & liquid cooling
Practice live readings and switching in "NOC Alarm Storm & 1ms SOE Triage" with no login required.
Primary standards & technical references