Open-Transition vs Closed-Transition Transfer
Plain-English definition
Two methods of switching an electrical bus between live AC sources: open-transition (break-before-make) opens the outgoing breaker completely before closing the incoming breaker, whereas closed-transition (make-before-break) briefly parallels synchronized sources, often for under 100 milliseconds, for uninterrupted transfer.
Why it matters on shift
Closed-transition retransfers smoothly return loads from generators back to restored utility power without cycling chillers or UPS batteries, provided ANSI 25 sync-check permissives and short-circuit fault ratings allow momentary overlap.
Illustrative operational example
In an illustrative post-outage utility return, an ATS waits 5 minutes to confirm utility stability, verifies phase difference within ±2.0° via ANSI 25, overlaps utility and generator for 80 ms, and opens the generator breaker.
Scope, code & safety boundary
Electric utilities often restrict closed-transition overlap duration and require fail-to-open protective trip timers so two sources never stay paralleled indefinitely.