Relative Humidity (RH)
Plain-English definition
The percentage ratio of actual water-vapor partial pressure in air to the maximum saturation vapor pressure air could hold at that exact dry-bulb temperature. Because warm air can hold much more moisture, heating air across a server lowers its relative humidity even when absolute moisture stays constant.
Why it matters on shift
Excessively low humidity increases electrostatic-discharge precautions, while excessive relative humidity accelerates hygroscopic dust bridging and copper/silver corrosion on circuit boards, especially if corrosive gases are present.
Illustrative operational example
Air entering a server at an illustrative 20°C and 50% RH (9.3°C dew point) exits the server rear at 34°C with the exact same 9.3°C dew point, but its relative humidity drops to roughly 22%.
Scope, code & safety boundary
Current ASHRAE Chapter 20 Table 1 note (n) sets recommended upper RH conditionally: up to 70% RH only in verified low-corrosion (G1) environments, versus 50% RH where corrosion risk is higher or unverified, not a blanket 60% rule.